UNINYVIN CABLE

Application

These cables are used in UPS systems and server rooms as the nylon and fiber glass braid on the cable does not allows the heat generated in
the conductor, due to continuous operation, to be felt in the surrounding areas. These cables are widely used in aircraft cabling.

Cable Construction

Conductor : Annealed tinned copper to IS:10241 Part 3, uniformly bunched to form a circular shape
Insulation : Special core insulation HR-PVC 105° C
Primary Braid : Braided with glass fiber, 100% coverage
Secondary Braid : Braided with nylon fiber, 100% coverage
Lacquer : Overall construction is finally lacquered with nylon varnish

Properties

Max. Operating Voltage : 600V r.m.s.
Operating Temperature Range : -35°C to 105°C
Resistant to ester based fluids (hydraulic oil), acids, chemicals and solvents. The nylon and glass fibers are very good heat resistant materials.

Cable Design Parameters

Part NumberCable SizeConductorRadial ThicknessNylon Braidand LacquerOverall Diameter of CableDC
Conductor
Resistance
at 20°C
(Ω/km)
Max. Current Rating (Amps.) – BS G 177
Nom.Cross
Sectional
Area
(Sq. mm)
No. & Dia.of Wiresin (mm)Max.
Conductor
Diameter
(mm)
Min.
Conductor
Diameter
(mm)
Min.
PVC
Insulation
Max.(mm)Min.(mm)Max.(mm)Min.(mm)
120401050001142.0570/0.1931.9561.8030.2790.1780.0763.439.231
120401060001123.22110/0.1912.4382.2860.2790.1780.0763.83.55.8543
120401070001105.3373/0.3053.152.8960.3810.3810.1275 4.63.53261
12040108000188.76120/0.3053.2423.9370.3810.3810.1276.35.92.15487
120401090001613.3182/0.3055.5375.080.3810.3810.1277.67.31.422115
120401100001421.5294/0.3056.9096.4520.4830.3810.1279.38.80.877160
120401110001233.3203/0.4578.7638.1280.4830.3810.12711.010.50.565200
120401120001140.7248/0.4579.7549.1190.5590.3810.12712.211.70.463220
120401130001053.0323/0.45710.97310.3380.6350.3810.12713.713.00.355240
1204011400010068.3416/0.45712.44611.6840.6860.3810.12715.414.60.276270

Table I : Current Ratings for Multiple Circuits

Cable SizeNominal Cross Sectional Area (Sq. mm)Max. Current Rating (Amps)
Single Cable3 – Bunched Cables7 – Bunched Cables12 – Bunched Cables
142.0540312215
123.2255382819
105.3378604832
88.76111836346
613.314811183
421.5205153117
233.3256198153
140.7282210166
053308236210
0068.3346268238

Note :
1) The current rating mentioned in Table I are for bunched cables in free air at 40 °C.
2) Derating factors mentioned in Table II, shall to be used for higher ambient temperature.

Table II : Derating Factor of Uninyvin Cable for Different Ambient Temperature

Ambient temp. (°C)404550556065707580859095100
Derating factor1.00.960.920.880.830.780.750.730.680.620.530.480.3

Table III : Maximum 1 Minute Current Ratings for Multiple Circuits

Cable SizeNominal Cross Sectional Area (Sq. mm)Max. Current Rating (Amps)
Single Cable3 – Bunched Cables7 – Bunched Cables12 – Bunched Cables
142.0550474342
123.2272676260
105.33110107104101
88.76173165159153
613.3250236230
421.5390378360
233.3545530520
140.7620600590
053705690680
0068.3820810800

Table IV : Test for Resistance to Fluids

Sr. No.Fluid RepresentedTest FluidsTemp. of TestMax. Change in Dia. %
1Aviation Turbine FuelKerosene20 ± 0.55
2Fuel70% ISO Octane 30% Toluene by Vol.20 ± 0.55
3HydraulicFluid 80% Ethylene Glycol Mono Ethyl Ether, 20% Castor Oil by Vol.50 ± 25
4Ester Based Lubricating OilEster Based Hydraulic Fluid100 ± 25

Note:
1) Uninyvin cables as per BS G 177 are meant for air craft (cabling) flying under tropical weather conditions .