UL 1569

Application

These cables are used for internal wiring of switchboards, electronic and electrical equipment, e. g. households, radio of televisions, monitor and control desks.

Technical Data

Standard : UL – Std. 758 , CSA C 22.2 No.210
Nominal Voltage : 300V
Test Voltage : 2000V
Test Voltage (spark test)
AWG 26 – 20 : 4kV, AWG 10 -18: 5kV
Temperature Range : Flexible -5°C to + 105°C. Fixed installation -20°C to + 105°C
CSA – AWM I A/B
Bending Radius : Flexing 10 x cable ø. Fixed installation 5 x cable ø

Cable Construction

Annealed plain or tinned stranded copper conductor.
PVC – core insulation according to UL – Standard 1581, Class 43 Tab. 50.182, heat and damp resistant.

Properties

Conditionally resistant to oils, solvents, acids and dyes.
PVC self – extinguishing and flame retardant, test method to UL VW-1 and CSA FT 1 / FT 2

Cable Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the insulation colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 -Violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey,
13 – light blue.

Part NumberAWG No.No. of Cores & Nominal Cross Sectional Area (Sq. mm)Approx. Cable Diameter (mm)Approx. Copper Weight (kg/km)Approx Cable Weight (kg/km)
06040101xx30261 x 0.141.31.43.0
06040102xx30241 x 0.211.52.14.3
06040103xx30221 x 0.331.63.55.8
06040104xx30201 x 0.521.85.28.0
06040105xx30181 x 0.822.18.312
06040106xx30161 x 1.322.513.518.4
06040107xx30141 x 2.083.020.427.3
06040108xx30121 x 3.313.532.541.3
06040109xx30101 x 5.264.151.762.8

Reviews