AYY/YY-2 CORE

Cable Construction

1.1 kV (A.C) & 1.5 kV (D.C ) to Earth
2 cores AL / CU conductor, PVC insulated, unarmoured cables as per IS 1554 Part – 1.
Conductor : AL up to 10 Sq. mm conductor are solid Cl. 1 as per IS 8130. And above 10 Sq. mm conductor are stranded round or compact round or Compact shape conductor Cl. 2 as per IS 8130
In CU 4 & 6 Sq. mm conductor are solid Cl. 1 or stranded round Cl. 2 as per IS 8130. 10 Sq. mm conductor is stranded round or stranded compact conductor Cl. 2 as per IS 8130
Above 10 Sq. mm conductor are stranded round or compact round or compacted shaped Cl. 2 as per IS 8130
Insulation : PVC Type – A, as per IS 5831.(Option : HR PVC Type – C, as per IS 5831)
Core Color : Red, black
Inner Sheath : PVC / PVC tape as per IS 1554 (P – 1)
Outer Sheath : PVC Type ST – 1 as per IS 5831 (Option : PVC Type – ST – 2 as per IS 5831 / FR Type / FRLS Type)
Cable Color : Black (Options : Any other color as per requirement)

Cable Design Parameters

While ordering, in addition to the part number the following details shall also be advised:
Conductor Type (Aluminium or Copper) and class of conductor (Cl. 1 or 2).
Insulation Type – PVC Type A / C.
Sheath Type – PVC Type ST – 1 / FR / FRLS; PVC Type ST – 2 / FR / FRLS.

PartNumberNominal Cross Sectional Area(Sq. mm)Minimum No. of Strands in ConductorNominal Thickness of Insulation (mm)Minimum Thickness of Inner Sheath (mm)Nominal Thickness of Outer Sheath (mm)Approx.Overall Diameter(mm)Approx. Net Wt.of Cable (Kg/Km)
ALCUAL CableAYYCU CableYY
1102002000044_1/71.00.31.814240290
110200200006611/71.00.31.817300370
11020020001010161.00.31.818400520
11020020001616661.00.31.817430630
11020020002525661.20.32.019450750
11020020003535661.20.32.021550980
11020020005050661.40.32.0247001300
1102002000707012121.40.32.0268501700
1102002000959515151.60.42.23011502300
11020020012012015181.60.42.23213002800
11020020015015015181.80.42.43416003450
11020020018518530302.00.52.43820004300
11020020024024030342.20.52.64225005500
11020020030030030342.40.62.84630006700
11020020040040053532.60.73.25238008750
11020020050050053533.00.73.454480011000
11020020063063053533.40.73.865600013800

Electrical Parameters

PartNumberNominal Cross Sectional Area(Sq. mm)Max. DC Conductor Resistance at 20°C (Ω/km)Max. AC Conductor Resistance at 70°C (Ω/km)Approx. Reactanceat 50 Hz (Ω/km)Approx. Capacitance of Cable (microF/KM)Approx. Net Wt.of Cable (Kg/Km)Short Circuit Current Rating for 1sec. Duration(K.Amps)
ALCUALCUWith AL Cond.With CU Cond.
GroundDuctAirGroundDuctAirALCU
1102002000044_4.61_5.530.0980.233428304437390.3040.46
11020020000664.613.085.533.70.0960.284337405547500.4560.69
110200200010103.081.833.72.20.0910.345748537461670.761.15
110200200016161.911.152.291.380.0850.407861709478851.221.84
110200200025251.20.7271.440.870.0830.429580991201001251.92.88
110200200035350.8680.5241.040.630.0820.48116941171451201552.664.03
110200200050500.6410.3870.7690.4640.0820.491401101401701451903.85.75
110200200070700.4430.2680.5320.3220.0760.561701401762101752355.328.05
110200200095950.320.1930.3840.2320.0760.582001652212502102907.2210.90
1102002001201200.2530.1530.3040.1840.0750.632251852582852403309.1213.80
1102002001501500.2060.1240.2470.14880.0740.6325521029431527037511.417.30
1102002001851850.1640.09910.1970.11890.0740.6428523533935530043514.121.28
1102002002402400.1250.07540.1510.09120.0730.6732527040241035051018.227.6
1102002003003000.10.06010.1220.07330.0730.6837030546146039059022.834.5
1102002004004000.07780.0470.09610.0580.0720.7043535054252044067030.446.0
1102002005005000.06050.03660.07590.04590.0720.704814056245804807503857.5
1102002006306300.04690.02830.0610.03680.0720.7053747072368057587547.972.55