UL 1015

Application

These cables are used for internal wiring of panels and electrical equipment. These are used as connection wire in machines laid in protective tubes and flexible pipes and also for motors and transformers.

Technical Data

Standard : UL – Std. 758, CSA C 22.2 No. 210
Nominal Voltage : 600V
UL – type AWM 105°C 600V
CSA – type AWM 105°C 600V
Test Voltage (Spark Test)
AWG 24 : 4kV
AWG 22 and 20 : 5kV
AWG 18 to 16 : 6kV
≥ AWG 8 : 7.5kV
Temperature Range : Flexing -5°C to +105°C. Fixed installation -20°C to +105°C
Temperature at Conductor : Max. UL and CSA : +105°C
Bending Radius : Flexing 10 x cable ø’. Fixed installation 5 x cable ø

Cable Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the insulation colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 -Violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey.

Part NumberAWG No.No. of Cores & Nominal Cross Sectional Area (Sq. mm)Approx. Cable Diameter (mm)Approx. Copper Weight (kg/km)Approx Cable Weight (kg/km)
06020101xx30241 x 0.212.22.17
06020102xx30221 x 0.332.43.59
06020103xx30201 x 0.522.55.211
06020104xx30181 x 0.822.88.316
06020105xx30161 x 1.323.113.522
06020106xx30141 x 2.083.520.431
06020107xx30121 x 3.314.032.545
06020108xx30101 x 5.264.651.768
06020109xx3081 x 8.356.282.5113
06020110xx3061 x 13.38.0132.1184
06020111xx3041 x 21.149.4207.3275
06020112xx3031 x 26.6510.2262.0339
06020113xx3021 x 33.6111.0330.3416
06020114xx3011 x 42.3813.0416.9543
06020115xx301/01 x 53.4713.8524.6659
06020116xx302/01 x 67.415.2661.0820
06020117xx303/01 x 85.016.5832.31013
06020118xx304/01 x 107.218.01050.91257
06020119xx30250 kcmil1 x 12720.01245.01507
06020120xx30300 kcmil1 x 15221.41489.81780
06020121xx30350 kcmil1 x 17822.61734.62048
06020122xx30400 kcmil1 x 20324.01989.92338
06020123xx30500 kcmil1 x 25426.02479.52868