6181Y – BS 6004

Application

The cables are suitable for power and lighting circuits and building wiring suitable for use in semi flush exposed conduits, embedded
conduits and in closed installation ducts. Ideal for internal wiring of appliance.
Standard
EN 50363-3 with BS 7655-4.2 (Only for sheath).

Technical Data

Voltage Rating : 1.5 mmsquare to 35 mmsquare – 300 / 500V
Temperature Range : -15°C to 70 °C
Minimum Bending Radius
Upto 10 mm2 : 10 X Overall Diameter.
16 & 35 mm2 : 12 X Overall Diameter.
16 & 35 mm2 : 12 X Overall Diameter.
Test Voltage : 2 kV for 15 min

Cable Construction

Conductor :
Plain annealed copper conductor : 1.5 & 2.5 mm2 Class -1, 4.0 to 35 mm2 stranded Class 2 complying with BS EN 60228, HD 383, IEC 60228.
Insulation : PVC (Polyvinyl Chloride ) compound type TI 1 complying with EN 50363-3
Sheath : PVC (Polyvinyl Chloride ) compound type Type 6 complying with BS 7655-4.2
Insulation Colours : Blue and brown
Sheath Colour : Grey RAL 7001

Cable Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required: 04 – blue, 09 – brown

Part NumberNominal Cross Sectional Area (Sq. mm)Nominal Insulation Thickness (mm)Nominal Sheath Thickness (mm)Overall Diameter Lower Limit (mm)Overall Diameter Upper Limit (mm)Approx. Net Weight (kg/km)
01150101xx101.50.700.84.205.0037
01150102xx102.50.800.84.805.7051
01150103xx1040.800.95.506.7075
01150104xx1060.800.96.007.3098
01150105xx10101.000.97.308.80152
01150106xx10161.001.08.4010.10220
01150107xx10251.201.110.0012.10336
01150108xx10351.201.111.1013.50353

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required: 04 – blue, 09 – brown.